Opis
Protuprovalni prigušnik za zaštitu potrošačkih instalacija.
Ovaj tekst je strojno preveden.
Varnost izdelkov (GPSR)
Proizvajalčeva koda: 158332
EAN koda: 4015081549207
Registrirana blagovna znamka: Eaton
Ime proizvajalca: Eaton Electric GmbH
Naslov proizvajalca: Hein-Moeller-Str. 7-11
Poštna številka proizvajalca: 53115
Kraj proizvajalca: Bonn
Država proizvajalca: Germany
Telefon proizvajalca: +496951709895
Elektronski kontakt proizvajalca: https://www.eaton.com
Kontakt odgovorne osebe za varnost: [email protected]
Država odgovorne osebe za varnost: Nemčija
Dokumenti
Tehnički podaci
| Vrsta proizvoda |
odvodnik za prenaponsku zaštitu |
|---|---|
| Zaštita od prenapona za |
razdjelni ormar |
| Nazivni napon |
280 V/AC |
| Izvedba |
4-polna |
| Vrsta zaštite |
IP20 |
| Proizvođač-br. dijela |
158332 |
| Sadržaj |
1 St. |
| Mounting method |
DIN rail (top hat rail) 35 mm |
| Lightning impulse current (10/350 µs) |
12.5 kA |
| Number of poles |
4 |
| Construction size |
5 modular spacing |
| Voltage protection level |
0 kV |
| Remote signalling |
FALSE |
| Follow current extinguishing capability |
0 kA |
| Max. continuous voltage AC |
280 V |
| Nominal voltage AC |
280 V |
| Nominal voltage DC |
0 V |
| Test class |
Type 1 + 2 |
| Voltage protection level L-N |
1.5 kV |
| Signalling at the device |
Optical |
| Max. continuous voltage DC |
0 V |
| Degree of protection (IP) |
IP20 |
| Max. PV-voltage |
0 V |
| Voltage protection level N-PE |
100 kV |
| Integrated backup fuse |
FALSE |
| Max. conductor cross section solid (solid, stranded) |
25 mm² |
| Max. conductor cross section flexible (fine-strand) |
35 mm² |
| Voltage protection level (DC+ - DC-) |
0 kV |
| Voltage protection level (DC+/DC- - PE) |
0 kV |
| Specific energy (W/R) |
2500 kJ/Ohm |
| Energy-coordinated protection effect with regard to the terminal equipment |
FALSE |
| System configuration DC |
FALSE |
| System configuration IT |
TRUE |
| System configuration TN |
TRUE |
| System configuration TN-C |
FALSE |
| System configuration TN-S |
TRUE |
| System configuration TT |
TRUE |
| System configuration other |
TRUE |
| System configuration TN-C-S |
FALSE |
| Voltage protection level L-PE |
1.5 kV |
| Max. overcurrent protection device, parallel connection (fuse) |
0 A |
| Max. overcurrent protection device, series connection (fuse) |
0 A |
| Voltage switching spark gap technology |
TRUE |
| Overcurrent protected voltage tapping |
FALSE |

0 od 5